Application: Emergency model for premises with danger of explosion. Light fixture is certified by FTZU Ostrava-Radvanice (certificate FTZU 04 ATEX 0219X).
Ballast: EP – electronic ballast 220-240 V/50-60 Hz AC, 220-240 V DC, 176- 280 V DC (min. discharge ignition voltage of lamp ≥ 198 V DC). Emergency unit 230 V/50 Hz.
Body: Plastic material PC (polycarbonate), grey colour RAL7035.
Cover: Plastic material PC (polycarbonate), transparent colour.
Reflector: White painted metal sheet RAL 9003.
Fastening: Direct fastening on ceiling or wall lighted area by means of ceiling fastening brackets (basic equipment), suspension with self-locking suspenders.
Connection: Screwless three-pole terminal block, max. diameter of wires 2,5 mm2; light fixture is ready to connect two wires (order additional cable gland).
Standard equipment: 1 pc sealing cable gland, 3 pcs sealing plug, 2 pcs fastening spring, double clamp for power cables, stainless steel clips, compact fluorescent lamp DULUX S/E 9 W or DULUX S/E 11 W, pictograms.
On request:
Marking: Maintained emergency lighting (MULTI), non-maintained emergency lighting (Em).
Code number | Description | Type of source | A (mm) | B (mm) | C (mm) | Weight (kg) |
---|---|---|---|---|---|---|
052022 | BASET-N-PC-109, 1x9W, 3h, 2G7 | TC-SEL / 2G7 | 338 | 173 | 105 | 1,5 |
052040 | BASET-N-PC-111, 1x11W, 3h, 2G7 | TC-SEL / 2G7 | 338 | 173 | 105 | 1,48 |
052030 | MULTIBASET-N-PC-109-EP, 1x9W, 3h, 2G7 | TC-SEL / 2G7 | 338 | 173 | 105 | 1,54 |
052031 | MULTIBASET-N-PC-111-EP, 1x11W, 3h, 2G7 | TC-SEL / 2G7 | 338 | 173 | 105 | 1,64 |
Brands | VYRTECH |
---|---|
Select Model | 052022, 052030, 052031, 052040 |